Compensation of Voltage Sags Due to Short Circuits on Distribution Lines (Feeders) with Dynamic Voltage Restorer (DVR)
DOI : DOI: 10.56347/jes.v5i1.418
Date : 6 August 2026
Short circuit faults occur frequently on distribution lines. Such faults generate a fault current within a short interval and result in a momentary voltage drop, commonly known as a voltage sag. On a feeder, the short circuits that occur most often are single-phase-to-ground, two-phase, and three-phase faults. To determine the voltage sag on the line caused by a short circuit, it is necessary to analyze the short circuit fault current and voltage sag by assuming the fault point at 25%, 50%, 75%, and 100% of the total length of the BA 15 feeder. The voltage sag when a single-phase-to-ground short circuit occurs at 25%, 50%, 75%, and 100%, respectively, is 8663.68â 0° V, 5773.4â 0° V, 2886.87â 0° V, and 525.48â 0° V. When a two-phase short circuit occurs, the voltage sag is 19022.602â 0° V, 16637.035â 0° V, 12106.47â 0° V, and 11826.98â 0° V, while during a three-phase short circuit it is 5000â -76.05° V, 10000â -70.21° V, 15000â 67.05° V, and 18231.99â 24.29° V. This voltage sag disturbance can be corrected using a DVR, which injects the voltage required to restore normal conditions.